Interposing Current Transformer

We're here to help

Talk to an expert today.
Our friendly team of highly trained specialists will quickly assist you.

Get a quote technical support +61 (0) 2 8045 5185

Description

Interposing types can be used to modify the secondary current from an existing line CT. This is useful for modifying secondary currents without replacing the line CTs.

The main function of an interposing CT is to balance the currents supplied to the relay where there would otherwise be an imbalance due to the ratios of the main CTs. Interposing CTs are equipped with a wide range of taps that can be selected by the user to achieve the balance required.

As the name suggests, an interposing CT is installed between the secondary winding of the main CT and the relay. They can be used on the primary side or secondary side of the power transformer being protected, or both. Interposing CTs also provide a convenient method of establishing a delta connection for the elimination of zero sequence currents where this is necessary.

Feel free to give us a call or email us with your specific requirements and we will be happy to custom build this CT for you.

Customisable Parameters:

  • Current Ratio
  • Class Accuracy
  • Burden
  • Maximum System Voltage
  • Frequency