Call us: +61 2 8283 6945

Project Description

SUIN SA2100 – Three Phase Power Quality Analyser

Introduction

The SUIN SA2100 is a comprehensive and cost effective instrument ideally suited for the electrical trades toolbox and intended to monitor your electrical supply and diagnose Power Quality issues on-site and in real-time. It is battery operated and therefore offers the flexibility of a handheld multi-meter.

Suin logger1 CHK Suin logger2CHK

Key Features

  • Safety: CAT III 1000V / CAT IV 600V
  • Standards: IEC61000-4-30 (2008) S class EN50160 (2007)
  • Single-phase 2 W / Single-phase 3 W / 3-phase 3 W / 3-phase 4 W
  • Monitors four (4) voltages and currents
  • Display: Run Chart, Bar Chart, Vector Graphic, Waveform, Event List, Readings
  • Harmonics and interharmonics, flicker, transient capture, three-phase unbalance (voltage and current), dips and swells, voltage rapid change, and interruption
  • LAN interface PC can keep real-time remote communication
  • Built-in 8G memory card, USB port, LAN port for real-time remote control functionality and data download

 

1.1.3 Current Sensor Options

 

Description

Part Number

5A Clamp-On CT

SUC8C-5A

50A Clamp-On CT

SUCTC0080

100A Clamp-On CT

SUCTC0130

1000A Clamp-On CT

SUCTC1535

3000A Flexible Rogowski Coil

SUJK-3000A

Suin logger clamp on CT's

 

Suin SA 2100 Power Quality Analyser and Accessories

Kit Items

 

Description

Part Number

Quantity

SA2100 Power Quality Analyser

SU2100PQA

1

Program Software for PC (CD)

SU2100CD

1

2m voltage cable with 4mm banana plug

SU2100VL

5

Alligator Clips

SU2100CC

5

External DC Power Adaptor

SU2100PA

1

External DC Adaptor

SU2100PC

1

Carry Bag

SU2100BAG

1

Hang Strap

SU2100HS

1

Current Sensors

4 (select option)

Specifications

 

Measurement Range Resolution Accuracy
Voltage/Current/Frequency
Channel 3-phase line input + 1 neutral line input
Vrms(dc+ac) 1 ~ 1000Vrms 0.1Vrms ±5%
Vpk 1 ~ 1400Vpk 0.1Vpk ±5%
V(CF) 1.0 ~ >2.8 0.01 ±5%
Arms 1~ 3000A 1A ±1% ± 5digits
1~ 300A 0.1A ±1% ± 5digits
Apk 1 ~ 4000Apk 1A ±1% ± 5digits
A(CF) 1 ~ 10 0.01 ±5%
Frequency 42.5~57.5Hz(50Hz nominal) 0.01Hz ±0.01%
51~69Hz(60Hz nominal) 0.01Hz ±0.01%
Dips & Swells
Vrms1/2 0 ~ 200% of nominal voltage 0.1Vrms ±1%
Arms1/2 1 ~ 3000A 1A ±1% ±5 counts
1 ~ 300A 0.1A ±1% ±5 counts
Threshold levels Programmable thresholds in percent of nominal voltage
Event detection based upon ½ cycle rms voltages
Captures Dips, Swells Interruptions and Rapid Voltage Changes
Duration hhh,mm,ss,mmm 0.5 cycle 1 cycle
Harmonic
Harmonic Order 1 ~ 50
Inter-Harmonic Order 1 ~ 49
Voltage 0.0 ~ 100.0% 0.1% ±0.1% ± nx0.1%
Current 0.0 ~ 100.0% 0.1% ±0.1% ± nx0.1%
THD 0.0 ~ 100.0% 0.1% ±2.5%
DC Relative 0.0 ~ 100.0% 0.1% ±2%
Frequency 0 ~ 3500Hz 1Hz 1Hz
Phase -360° ~ 0° ± nx1.5°
Power And Energy
Active Power/Apparent Power/Reactive Power 1.0 ~ 20.00MW 0.1kW ±1.5±10 counts
Energy 0.00kWh ~ 200GWh 10Wh ±1.5±10 counts
Power Factor 0 ~ 1 0.01 ±0.03
Flicker
Pst(1min),Pst,Plt,PF5 0.00 ~ 20.00 0.01 ±5%
Unbalance
Voltage 0.0 ~ 5.0% 0.1% ±0.5%
Current 0.0 ~ 20.0% 0.1% ±1%
Voltage Phase Angle -360° ~ 0° ±2digits
Current Phase Angle -360° ~ 0° ±5digits
Voltage Transient
Vpk ±6000Vpk 1V ±15%
Vrms 10 ~ 1000Vrms 1V ±2.5%
Min. Tested Time 50us
Sampling Rate 20kS/s
Inrush Current
Arms(AC+DC) 0~3000Arms 0.1 ±1% ± 5digits
Inrush Duration 6s ~ 32min selectable 10ms ±20ms
Logger
Recording Parameter, duration time and time interval can be set by user, which can be export on PC
Memory 8G
Max. recording time 1 year
System Monitor
Parameters Vrms,Arms,Harmonic Volts,THD Volts,Plt,Vrms1/2,Arms1/2,Vneg,Hz,dips and swells, unbalance
Record Time 2h ~ 7days
Record Event Number >10000
Limits According EN50160  or customer definable
General Characteristics
Power AC220V(1±10%), 50Hz(1±5%), ≤10VA
Interface USB_HOST, LAN
Display 5.6′ TFT LCD, 320*240
Battery 7.4V, 4.4Ah, > 7 hours working time
Dimension & Weight 262×173×66mm, 1.6kg

 

Download the datasheets and manuals for SA2100 Power Analyser and accessories through our download centre

FacebookTwitterGoogle+Share
Back to Top